Electromagnetic Valve

Retail price
0.0
Market price
0.0
◆ The two-position three-way solenoid valve is the main starter component of the system. The gas is delivered to the pilot valve of the deluge system through the solenoid valve to keep the system closed. When a fire occurs, the central control system opens the solenoid valve remotely, the gas is released, and the deluge system opens immediately; when it needs to be closed, the central control system restores to the original state, and the system can only be closed by pressing the manual reset button of the solenoid valve after it is confirmed on the site that the fire alarm has been relieved. The solenoid valve has passed the SIL3 Safety Integrity Level certification.
Product serial number
Quantity
-
+
Stock:
0
1
Product description
Parameters

Electromagnetic Valve

◆ The two-position three-way solenoid valve is the main starter component of the system. The gas is delivered to the pilot valve of the deluge system through the solenoid valve to keep the system closed. When a fire occurs, the central control system opens the solenoid valve remotely, the gas is released, and the deluge system opens immediately; when it needs to be closed, the central control system restores to the original state, and the system can only be closed by pressing the manual reset button of the solenoid valve after it is confirmed on the site that the fire alarm has been relieved. The solenoid valve has passed the SIL3 Safety Integrity Level certification.

 

Technical Parameters

Material:316SS
Working pressure:10bar
Air connection size:1/4NTPF
Temperature:-20℃ to +180℃
Explosion protection level:Exd IIC T6 ,IP67
Opening method: Optional power-on or power-off as required
Reset method: manual reset
Electrical Interface:1/2NPTF
Power:24VDC,6.5W

 

Installation and maintenance

The solenoid valve is the most important component in the deluge system. It should be installed and wired by qualified and trained personnel. The coils should be connected in accordance with applicable standards such as IEC or ATEX specifications. It is necessary to make sure that the voltage and frequency are consistent with what is marked on the enclosure label.
Warning:only an authorized electrician should be allowed wire this product. When assembling the product, please use suitable tools to support the wire box of the housing. When tightening the fittings into the wire box, be careful that the maximum torque should not exceed 20Nm.
Maintenance:it is necessary to regularly check whether the solenoid valve is operating normally. When being used, the solenoid valve should be tested and maintained in accordance with the specific IOM (Installation Operation and Maintenance) manual of the Bermad valve. It is recommended to check the correct wiring and sealing of the solenoid valve every month. The solenoid valve must be tested once a year. The maximum working pressure must be applied to the system to simulate extreme environments. If a device fails, it should be replaced.

 

 


KF-SC-FM-DS-N01

Scan the QR code to read on your phone
We could not find any corresponding parameters, please add them to the properties table

Since its establishment, KinFire Technology has a wide range of achievements in the fields of petrochemical...

CONTACT

ADDRESS:

520 Chang'an Road, Wujiang Economic and Technological Development Zone, Suzhou

BUSINESS:

Monday to Friday: 8:30 a.m. - 5:30 p.m

TELEPHONE:

(86 512)6349 3119

WECHAT

IPHONE

Copyright KinFire Technology (Suzhou) Co., Ltd. © 2020  By www.300.cn   苏ICP备20025859号-1